DS 3.325
05/02
MA40-704X-G0X
MF40-7043-G0X
MS40-7043-G0X
Multi-Lingual Instructions
MLI 3.325 - Installation Instructions
Invensys is a trademark of Invensys plc and its subsidiaries and affiliates.
4Nm SPRING RETURN ROTARY ACTUATORS
Invensys Spring Return Actuators have a rotary output for direct
coupling to air dampers. Models are available for on/off operation from
230Vac or 24Vac power supplies and 24Vac Floating Point Control.
There is also a 2-10Vdc input version that is fully modulating.
A special feature of the design is that mounting brackets, universal
joints and linking rods are not required for normal damper applications,
thus reducing installation and commissioning time.
FEATURES
Direct coupling to all normal dampers without mounting
brackets or linkage kits - saves site time
Universal clamp provides direct mounting to damper shafts up
to 15mm diameter or up to 13mm square (AM-710 accessory
clamp required when mounting actuators to shafts up to 19mm
diameter or 13mm square)
Case to IP 54
Clockwise and Counterclockwise rotation available,
determined by Left or Right Hand mounting
Spring tensions whilst the damper is being operated
Positive spring return operation, for example under power
failure
Provides 95° of rotation; rotation limiting available
Visual position indicator
MX41-7043 Series actuators can be gang mounted to
accommodate high torque requirements
Optional built-in auxiliary switches to provide for interfacing or
switching
Cable Gland and Blanking plugs supplied fitted
MS4X-7XXX Series provided with Left/Right switch for selection
of direct or reverse action control mode.
Notes:
Using Invensys damper actuators
The actuators listed in this data sheet are intended for the operation of
air dampers in HVAC systems.
Torque requirements
When calculating the torque required to operate dampers, it is
essential to take into account all the data supplied by the damper
manufacturer concerning cross sectional area, design, mounting and
air flow conditions.
Page view 0
1 2 3 4 5 6 7 8

Summary of Contents

Page 1 - MS40-7043-G0X

DS 3.32505/02MA40-704X-G0X MF40-7043-G0X MS40-7043-G0XMulti-Lingual InstructionsMLI 3.325 - Installation InstructionsInvensys is a trademark of Invens

Page 2 - OPERATION

DS 3.325 2 - 8 05/02SPECIFICATIONSACCESSORIESAM-674 - Weather ShieldAM-675 - Base Mounting Plate for AM-674AM-676 - Universal Shaft Extension, to leng

Page 3 - Precautions (General)

05/02 3 - 8 DS 3.325INSTALLATIONThe actuator is fitted directly to the damper and the clamp tightened securely to the damper shaft. A universal anti-r

Page 4

DS 3.325 4 - 8 05/025. Secure the universal mounting clamp to the actuator using the retaining clip.6. Position the damper at its normal (spring retur

Page 5

05/02 5 - 8 DS 3.325Installation of Universal Shaft Extension AM-676Installation requires an AM-676 Universal Shaft Extension and two AM-710 Universal

Page 6 - CONNECTION DIAGRAMS

DS 3.325 6 - 8 05/02CONNECTION DIAGRAMSWARNING - THESE ARE SPRING RETURN ACTUATORS. KEEP CLEAR OF ALL MOVING PARTS WHEN POWER IS REMOVED. ONLY SWITCH

Page 7 - 05/02 7 - 8 DS 3.325

05/02 7 - 8 DS 3.325

Page 8 - DIMENSION DRAWING

DS 3.325 8 - 8 05/02Building Systems - UKInvensys Energy SolutionsFarnham RoadSloughBerkshire SL1 4UHUnited KingdomTelephone +44 (0)1753 611000Facsimi

Comments to this Manuals

No comments