Schneider Electric TAC Xenta 527-NPR User Manual

Browse online or download User Manual for Networking Schneider Electric TAC Xenta 527-NPR. TAC Xenta 527-NPR

  • Download
  • Add to my manuals
  • Print
  • Page
    / 2
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 0
TAC Vista
TAC Xenta 527-NPR
Security Router
03-00043-02-en
The TAC Xenta 527-NPR is a cost-effective and feature-enhanced version of the I/NET Net Plus Router. The TAC Xenta 527-NPR
carries out many of the functions of a host PC but at a controller level, which reduces any dependence on host computers. The NPR
deals with peer-to-peer point interaction, and manages and buffers events as necessary. All stored events and transactions are fully
protected against loss of power by onboard batteries. The Xenta 527-NPR only supports connections to I/NET networks. It does not
support LonWorks, or any other protocols.
This version of the Xenta 527-NPR introduces the ability to create segmented IP networks within an I/NET architecture. Encryption is
available at the Ethernet level for high security applications. Configuration is performed using I/NET, a serial terminal, or pre-defined
web pages. The Xenta 527-NPR does not require and is not supported by TAC XBuilder.
TECHNICAL DATA
Supply voltage..... 24 V AC ±20%, 50/60 Hz or 19–40 V DC
Power consumption.......................... max. 5 W
Transformer sizing ...............................5 VA
Ambient Temperature
Storage ...............–20 °C to +50 °C (–4 °F to +122 °F)
Operation .............±0 °C to +50 °C (+32 °F to +122 °F)
Humidity ..................max. 90% RH non-condensing
Mechanical
Enclosure....................................ABS/PC
Enclosure rating.................................IP 20
Flammability class, materials ...................UL 94 V-0
Dimensions ................................ see Fig. 1
Weight ...............................0.2 kg (0.44 lb.)
Real Time Clock
Accuracy at +25 °C ..................±12 minutes per year
Power failure protection ...........................72 h
Communication
A: RS232 ....................2400 – 57600 bps, RJ45, 8-p
A: RS485 ...........2400 – 57600 bps, async. terminal block
B: RS232 ...................................RJ10, 4-p
C: RS485 ....................sync. (SDLC) terminal block
LonWorks ......................TP/FT-10, terminal block
Ethernet.........................TCP/IP, 10Base-T, RJ45
Agency Compliances
Emission:
CE ..................................EN 61000-6-3
C-tick................................ C-Tick N1831
FCC ....................FCC Part 15, Subpart B, Class B
Immunity:
CE ..................................EN 61000-6-2
Safety:
CE ....................................EN 61010-1
UL 916.............................. C-UL US Listed
RoHS directive............................ 2002/95/EG
Part Numbers
TAC Xenta 527-NPR ........................007308210
Terminal part TAC Xenta 400..................007309020
TAC Xenta: Programming Serial Kit .............007309200
2 3 4 5 6 7 8 10
12 13 14 15 16 17 18 20
48 ± 0.5
(1.89 ± 0.02)
70 ± 2.0
(2.76 ± 0.08)10.1
(0.40)
4 (0.16)
90 (3.54)
110 (4.33)
77.4
(3.05)
45
(1.77)
Figure 1
PERFORMANCE
I/NET Network
The TAC Xenta 527-NPR has the capabil-
ity to act as a Net Plus Router within that
system. The TAC Xenta 527-NPR has
been tested to deliver up to a maximum
of 15 I/NET alarms/events/transactions
per second or 1.3 million per day. The
maximum burst can be up to 40 per
second for 8 seconds.
The thruput for a single TAC Xenta 527-
NPR is determined by the amount of
polling the device is managing. Polling is
created mainly by
• Pointsonopengraphicspages
• Thescanrateofconnectionobjects
• Thevolumeofalarmandeventtraffic
The physical size of the connected I/NET
system is a factor in this but is not a pri-
mary limitation.
In some systems therefore more than one
TAC Xenta 527-NPR may be required to
handle the total system traffic.