Diagnostics
Card fault
The [internal com. link] (ILF) fault appears when serious problems arise:
- Hardware fault in the Controller Inside card
- Dialog fault between the Controller Inside card and the drive
The drive behavior cannot be configured when an [internal com. link] (ILF) fault occurs, and the drive trips with freewheel stopping. This
fault cannot be reset.
Two diagnostic parameters can be used to obtain more detailed information on the origin of the [internal com. link] (ILF) fault:
- [Internal link fault 1] (ILF1) if the fault has occurred on option card no. 1 (installed directly on the drive).
- [Internal link fault 2] (ILF2) if the fault has occurred on option card no. 2 (installed directly on the drive).
The Controller Inside card can be in position 1 or in position 2.
Parameters [Internal link fault 1] (ILF1) and [Internal link fault 2] (ILF2) can only be accessed on the graphic display terminal, in the [1.10
DIAGNOSTICS] (DGT-), [MORE FAULT INFO] (AFI-) menu.
Value Description of the values of the [Internal link fault 1] (ILF1) and [Internal link fault 2] (ILF2) parameters
0 No fault
1 Loss of internal communication with the drive
2 Hardware fault detected
3 Error in the EEPROM checksum
4 Faulty EEPROM
5 Faulty Flash memory
6 Faulty RAM memory
7 Faulty NVRAM memory
8 Faulty analog input
9 Faulty analog output
10 Faulty logic input
11 Faulty logic output
101 Unknown card
102 Exchange problem on the drive internal bus
103 Time out on the drive internal bus (500 ms)