Installation and Wiring
128
35010372 02 03/2006
Power Cord
Preparation
Power Plug
Illustration
The following illustration shows the Power Plugs used.
The following table displays connection wires into the Power Plug:
Note:
Wherever possible, use wires that are 0.2 to 2.5 mm2 (24 - 12 AWG) in size for
the power cord, and twist the wire ends before attaching the terminals.
If the conductor’s end (individual) wires are not twisted correctly, the end wires
may either short loop to each other, or against an electrode. To avoid it, use
D25CE/AZ5CE cable-ends.
The Conductor Type is solid or stranded wire.
The following illustration shows the conductor length:
Connection Wire
+24V
-0V
FG Grounded Terminal connected to the XBT GT chassis.
Insertion
Direction
FG
-
+
nsertion holes
Power plug for XBT GT2000 and
4000 series
Power plug for XBT GT5000,
6000 and 7000 series