Notes The notes relating to this chapter are as follows:
1. The Data type property must correspond exactly to the actual data type of the variable.
If the Address property is the direct address of a binary PLC reference (reference 0x/
1x Quantum for example), the Data type property must be set to Coil for outputs or
Discrete Input for discrete inputs.
2. The various values of the Data type property have the following meaning:
Type de données Signification
COIL output bit (Boolean)
DISCRETE INPUT input bit (Boolean)
REGISTER 16-bit signed integer
REGISTER32 32-bit signed integer
INPUT REGISTER 16-bit signed integer for analog input
3. The limits of the Maximum PLC Value and Minimum PLC Value properties are the
natural limits of the configured Data type property.
4. For a push button you must specify at least one value. If several values are entered,
they will be assigned to an address table starting with the direct address indicated.
5. In the HTML code, by specifying param name = "label" value = "$data$", the applet
will display the numerical value of the data in place of a label.