Rotary Slider A rotary slider gives an analog representation of the value of a direct address of a
Modbus device. On a circular dial, it draws a position proportional to the value of the
address and represents a percentage of its range in physical units. The size of the
circular dial (cycle in degrees of a circle) and the color of the button can be
configured. Using the mouse, the user can change the value of the rotary slider and
trigger the sending of a new value to the PLC.
Setup:
The properties of the slider are as follows:
REGISTER
1
label
65535
0
0
180
0
65535
25
255
Maximum PLC Value
Minimum PLC Value
Border Width
Unit ID
Polling rate [ms]
Address
Data Type
Label
Major Scale Divisions
Minor Scale Divisions
Scale Precision
Dial Degrees Sweep
Cancel
OK
Properties [Rotary Slider]
100
Read Only
Maximum EU Value
1000
0
Minimum EU Value
FALSE
Property HTML code Description Limits
Address Address Modbus address of the data type (1 to 65535). See Note 1, (See
Notes, p. 162
)
Data type Datatype Modbus address data type. See Note 2, (See
Notes, p. 162
)
Label Label Label to be displayed as part of the graphic object. See Note 5, (See
Notes, p. 162
)
Major scale
graduation
MajorTics Number of major graduations (marked) in the scale. 0 to 100
Minor scale
graduation
MinorTics Number of minor graduations (not marked) in the scale. 0 to 100
Scale precision Precision Number of decimal places to be shown for the scale
graduations (set to -1 to use a general exponential format).
-1 to 6
Dial Degrees
Sweep
DegSweep Portion of circular dial to be used to draw the scale. 60 to 300
Maximum EU
Value
Maximum Maximum value, in physical units, of the direct address for
scaling.
Page view 157