11. Navigate back to the Mode screen and set the mode to Cool. Press [OK] and then press [Back].
Lower the desired cool setting below the current temperature. Ensure that the heat pump turns on
in cooling mode.
12. Navigate back to the Mode screen and set the mode to Off. Press [OK] and then press [Back].
Ensure that the cooling unit turns off.
13. Navigate back to the Mode screen and set the mode to Auto. Press [OK] and then press [Back].
14. Press [HOLD] and select Off to enable Energy Efficient Control.
Two Speed Heat Pump (3-Stage Heat / 2-Stage Cool)
Configuration
The “System Type” for this thermostat must be set to “Heat Pump” under “System Options.”
The “Cool Stages” and “Heat Stages” settings must be configured under “Stage Settings.”
Power Up
1. Double check the wiring. Be sure there are no stray wires or wire strands at the connections.
2. Turn on power to the transformer and system. The display will show the current thermostat
settings.
3. Press [TEMP], then press [MORE].
4. Scroll to Fan and press [OK].
5. Set the fan to On. Press [OK] and then press [Back]. The fan should turn on.
6. Navigate back to the Fan screen and set the fan to Auto. Press [OK] and then press [Back]. The
fan should turn off.
7. Press [MORE], scroll to Mode, and press [OK]. Set the mode to Heat. Press [OK], then press [Back].
8. Raise the desired heat setting 2 degrees above the current temperature. Ensure that the heat pump
turns on in heating mode. Press [HOLD] and select “On” to override Energy Efficient Control. Stage 2
heat should turn on.
Figure 9: Connections for Two-Speed Heat Pump Thermostat
Comp Stage 2 Relay
Comp Stage 1 Relay
Compressor Stage 2
9
5
4
1
3
8
6
7
11
12
(D)
(H)
(L)
(G)
(Y1)
(B)
(O)
(W2)
(C)
(RC)
UP
HVAC SYSTEM
THERMOSTAT
24 VAC
CONTROL
TRANSFORMER
Dehumidifier
Humidifier
Ground Fault
Fan
Compressor Stage 1
Energized in Heat
Energized in Cool
Auxiliary Heat
24 Vac Common*
24 Vac "HOT"
Aux Heat Relay
Reversing Valve
Fan Relay
Fault Relay
Humidifier
Dehumidifier
(Y2)
10