Configuration
The “System Type” for this thermostat must be set to “Zone Control” under “System Options.” The two
additional outputs (W2 and Y2) are used with zoned heating and cooling systems. The W2 and Y2
terminals control the one control panel mode of operation (heating or cooling). The zone control panel
recognizes calls for heat (W) from the individual zones when the W2 terminal is energized, and calls
for cool (Y) when the Y1 terminal is energized. Neither W2 nor Y2 is energized when the mode is set to
“OFF.” Therefore, the thermostat can act as a Master to set the operating mode of the entire system.
Power Up
1. Double check the wiring. Be sure there are no stray wires or wire strands at the connections.
2. Turn on power to the transformer and system. The display will show the current thermostat
settings.
3. Press [TEMP], then press [MORE].
4. Scroll to Fan and press [OK].
5. Set the fan to On. Press [OK] and then press [Back]. The fan should turn on.
6. Navigate back to the Fan screen and set the fan to Auto. Press [OK] and then press [Back]. The
fan should turn off.
7. Press [MORE], scroll to Mode, and press [OK]. Set the mode to Heat. Press [OK], then press [Back].
8. Raise the desired heat setting above the current temperature. Ensure that the heating unit turns on.
9. Navigate back to the Mode screen and set the mode to Off. Press [OK] and then press [Back]. The
heating unit should turn off.
10. Navigate back to the Mode screen and set the mode to Cool. Press [OK] and then press [Back].
Lower the desired cool setting below the current temperature. Ensure that the cooling unit turns on.
11. Navigate back to the Mode screen and set the mode to Off. Press [OK] and then press [Back].
Ensure that the cooling unit turns off.
12. Navigate back to the Mode screen and set the mode to Auto. Press [OK] and then press [Back].
Two-Stage Conventional (2-Stage Heat / 2-Stage Cool)
Figure 7: Connections for Two-Stage Conventional Thermostat
UP
Heat 1
Heat 2
24 Vac Common*
24 Vac "HOT"
Dehumidifier
Humidifier
Cool 2
Cool 1
Fan
24 VAC
CONTROL
TRANSFORMER
Heat 2 Relay
Heat 1 Relay
Cool 1 Relay
Fan Relay
Cool 2 Relay
Humidifier
Dehumidifier
THERMOSTAT
HVAC SYSTEM
12
11
7
6
8
3
1
10
(RC)
(C)
(W1)
(Y1)
(G)
(H)
(D)
(Y2)
4
(W2)