Cool/Heat Min On/Off
Cool/Heat Min On/Off are used to limit the on and off times of the cooling and heating system (in
minutes).
Stage Settings
NOTE: Before operating the thermostat, the “Cool Stages” and “Heat Stages” must be configured.
Cool Minimum On
The number of minutes the thermostat forces the cooling system to remain on
before turning off. Raising this number will increase the total time the cooling
system is on, but may allow the temperature to drift farther from setpoint.
When combined with Cool Minimum Off, cycles per hours can be obtained by
using the following calculation:
60 / (Cool Minimum On + Cool Minimum Off). The default time is 6 minutes.
Cool Minimum Off
The number of minutes the thermostat forces the cooling system to remain off
before starting again. Raising this number will increase the total time that the
cooling system is off, but may allow the temperature to drift farther from the
setpoint. When combined with Cool Minimum On, cycles per hours can be
obtained by using the following calculation:
60 / (Cool Minimum On + Cool Minimum Off). The default time is 6 minutes.
Heat Minimum On
The number of minutes the thermostat forces the heat to remain on before
turning off. Raising this number will increase the total time the heating system
is on (saving energy), but may allow the temperature to drift farther from the
setpoint (decreasing comfort). When combined with Heat Minimum Off, cycles
per hours can be obtained by using the following calculation:
60 / (Heat Minimum On + Heat Minimum off). The default time is 6 minutes.
Heat Minimum Off
The number of minutes the thermostat forces the heat to remain off before
starting again. Raising this number will increase the total time that the heating
system is off (saving energy), but may allow the temperature to drift farther
from the setpoint (decreasing comfort). When combined with Heat Minimum
On, cycles per hours can be obtained by using the following calculation:
60 / (Heat Minimum On + Heat Minimum off). The default time is 6 minutes.
Cool Stages
The number of cool stages the HVAC system can support. The default setting
is 1.
Heat Stages
The number of heat stages the HVAC system can support. Auxiliary heat is
included in this number for heat pumps. The default setting is 1.