Use with HAI Home Control Systems
The thermostat can be connected to a Home Automation, Inc. (HAI) Home Control system. The HAI
controller can send commands to the thermostat to change mode, cool setting, heat setting, status of
fan and hold, and other items.
Run a three or four-conductor wire from the HAI system to the thermostat location. All thermostats on
an HAI Home Control system are connected to Ground, Zone +16, and Output 8. See Figure 11.
Notes:
1. Connect additional thermostats in parallel. They may be connected in home-run or daisy chain
configuration.
2. When connecting to an HAI Home Control system, the communications jumper (J8), labeled
“COMM JUMPER” on the thermostat printed circuit board, must be in place.
3. Connect all thermostats on an HAI controller to the GRN (Green), BLK (Black), and YEL (Yellow)
terminals under the section marked “TSTAT.”
4. Contact HAI for more information.
Figure 11: Connections to HAI Home Control Systems
THERMOSTAT
GND
CONTROLLER
Z16-
+Z15-+Z14-
+Z13-
+Z12-
UTS
PHONE
GRYBRNREDGRN7
GND
6
5
Black
Green
Yellow
UP
COMMUNICATIONS
JUMPER