  • TROUBLESHOOTING
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 13
12-EN © 2011 Schneider Electric All Rights Reserved
ENGLISH
9. Raise the desired heat setting 3 degrees above the current temperature. Auxiliary heat should turn on.
10. After a few minutes, navigate back to the Mode screen and set the mode to “EM heat.” Press [OK]
and then press [Back]. Both stages of the heat pump should turn off, but the auxiliary heat should
remain on.
11. Navigate back to the Mode screen and set the mode to Off. Press [OK] and then press [Back].
Ensure that the auxiliary heat turns off.
12. Press [HOLD] and select Off to enable Energy Efficient Control.
13. Navigate back to the Mode screen and set the mode to Cool. Press [OK] and then press [Back].
Lower the desired cool setting 2 degrees below the current temperature. Ensure that the heat
pump turns on in cooling mode.
14. Press [HOLD] and select “On”. Stage 2 cool should turn on.
15. Navigate back to the Mode screen and set the mode to Off. Press [OK] and then press [Back].
Ensure that the cooling unit turns off.
16. Navigate back to the Mode screen and set the mode to Auto. Press [OK] and then press [BACK].
17. Press [HOLD] and select Off to enable Energy Efficient Control.
Accessory Connections for Use with Remote Systems
This thermostat has been preprogrammed with energy saving program schedules. When used with a
remote system, Schneider Electric recommends that the Program Mode be configured as “None” or
“Occupancy.” This will disable the internal program schedules.
Setting The Communications Jumper
This thermostat comes from the factory with the communications jumper (J8), labeled “COMM
JUMPER” on the thermostat printed circuit board, installed. See Figure 10.
When connecting to a Home Automation, Inc. (HAI) Home Control system or remote switch, this
jumper must be installed.
When connecting to a PC or other device with a serial port, this jumper must be removed.
Figure 10: Communications Jumper
COMM JUMPER
J8
65A01 – Rev
SN
COMMUNICATIONS
JUMPER