Schneider Electric EER56100 Installation Guide Page 26

  • Download
  • Add to my manuals
  • Print
  • Page
    / 88
  • Table of contents
  • TROUBLESHOOTING
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 25
Schneider Electric USA, Inc.
8001 Knightdale Blvd.
Knightdale, NC 27545 USA
1-888-778-2733
www.schneider-electric.us
Electrical equipment should be installed, operated,
serviced, and maintained only by qualified personnel. No
responsibility is assumed by Schneider Electric for any
consequences arising out of the use of this material.
S1B14481 Rev. 01, 08/2011 Replaces S1B14481, 05/2011
© 2011 Schneider Electric All Rights Reserved
24-EN © 2011 Schneider Electric All Rights Reserved
ENGLISH
Product Support
The Schneider Electric Customer Care Center (CCC) is your single point of contact for information
about the Wiser EER56100 thermostat. Qualified personnel are available to answer your customer
service and technical support questions. Call toll free 1-888-778-2733.
Control By Remote System
Not Working
1. Check wires and connections to the section marked “Comm.”
2. Check thermostat address setting.
3. Check communications mode setting.
4. Check setup of the remote system.
NOTE: Ensure that all setup items for the thermostat and the remote
system are set to the proper configurations for communication.
Temperature Reading
Incorrect
1. Allow 30 minutes for thermostat to adjust.
2. Adjust calibration offset.
3. Change setup option to display °F or °C.
NOTE: After installation, allow the thermostat up to 30 minutes for
an accurate temperature reading.
Display Problem 1. Cycle power to the thermostat (R).
Auxiliary Heat On Too Often
1. Heat Pump is not able to meet load due to cold weather.
2. Thermostat is in EM Heat mode. Set thermostat to Heat or Auto
mode.
NOTE: In EM Heat mode, only the auxiliary heat is turned on.
Heat Pump Heats In Cool
Mode & Cools In Heat Mode
1. Reversing valve is connected to wrong terminal. Move the wire
from B to O or from O to B.
NOTE: The wires connecting the reversing valve may be reversed.
See Note 1 on page 9.
SYMPTOM ACTION TO TAKE