Schneider Electric EER56100 Installation Guide Page 7

  • Download
  • Add to my manuals
  • Print
  • Page
    / 88
  • Table of contents
  • TROUBLESHOOTING
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 6
5-EN© 2011 Schneider Electric All Rights Reserved
ENGLISH
Single-Stage Conventional
Configuration
The EER56100 is factory configured as a single-stage conventional heat/cool thermostat. In the factory
configuration, the thermostat does not turn the fan on with a call for heat. If the furnace does not turn the
fan on with a call for heat, the thermostat must be configured to do so under “System Options.”
Figure 4: Connections for Heat and Cool Transfers—Applies to All Systems
Figure 5: Connections for Single-Stage Heat/Cool Thermostat
UP
24 Vac Common
24 Vac Cool "HOT"
24 VAC
COOL
TRANSFORMER
24 Vac Heat "HOT"
24 VAC
HEAT
TRANSFORMER
REMOVE
JUMPER
THERMOSTAT
(C)
(RH)
(RC)
3
1
2
For HVAC systems
with separate heating
and cooling
transformers, remove
the metal jumper
between Terminal 1
(RC) and Terminal 2
(RH) on the left
terminal strip.
24 Vac "HOT"
Heat
24 Vac Common*
Fan
Cool
Humidifier
Dehumidifier
UP
24 VAC
CONTROL
TRANSFORMER
Dehumidifier
Humidifier
Fan Relay
Cool Relay
Heat Relay
HVAC SYSTEM
THERMOSTAT
(RC)
(C)
(Y1)
(G)
(W1)
(D)
(H)
1
3
8
6
7
11
12
* Common wire is
required in heat
only or cool only
applications. Also
use a common if the
heat, cool, or fan
relay cannot supply
15 mA to the power
thermostat without
activating.
Page view 6
1 2 3 4 5 6 7 8 9 10 11 12 ... 87 88

Comments to this Manuals

No comments