Program Options
This thermostat has been preprogrammed with energy saving program schedules. When used with a
remote system, Schneider Electric recommends that the Program Mode be configured as “None” or
“Occupancy.” This will disable the internal program schedules. The program options setting
determines the method for scheduling temperature change commands.
Calibration Offset
Calibration Offset is used to raise or lower the current temperature reading from the onboard
temperature sensor by 0.5 °F or 0.25 °C. The default setting is 0.00. The minimum calibration offset is
-14.5 °F and the maximum calibration offset is + 14.5 °F.
Cool/Heat Limits
Setpoints are used to limit the desired temperature settings in cool and heat mode. The desired cool
setting can never be set below the “Cool Setpoint Min.” setting, and the desired heat setting can never
be set above the “Heat Setpoint Max.” setting. The default setting for cool is 51 °F; cool setpoint
minimum is 48 °F, and cool setpoint maximum is 91 °F. The default setting for heat is 91 °F; heat
setpoint minimum is 45 °F, and heat setpoint maximum is 88 °F.
Program
Mode
*Schedule: Program setpoints are based on time of day and day of week.
None: The internal program schedule is disabled. Use this when connected to a
remote system for temperature change commands.
Occupancy: Program setpoints are based on the occupancy status of a remote system.
Status options are Day, Night, Away, and Vacation. This mode is also used
with a remote setback switch. NOTE: A remote system or switch is required.
An asterisk (*) next to a setup item indicates the default (factory) setting.